Types of wall tie and how they are spaced

The tie in your wall depends mostly on when the house was built, and each type fails in its own way. Here is how to tell them apart, and how far apart they should be.

Older houses have galvanised steel ties: vertical twist strips, butterfly wires or double triangle wires. Modern and replacement ties are stainless steel. Standard spacing for a typical house cavity is 900mm across and 450mm up.

Line drawings of four wall tie types: a vertical twist strip tie with fishtail ends, a figure-of-eight butterfly wire tie, a double triangle wire tie, and a straight helical remedial tie with a spiral profile.
The three common original tie types, and a helical tie of the kind used to replace them.

Ties found in older houses

TieWhat it looks likeHow it tends to fail
Vertical twistFlat steel strip about 20mm wide, twisted in the middle, often with fishtail endsRust on the outer end swells and lifts the brickwork above it, causing horizontal cracks
ButterflyThin galvanised wire bent into a figure-of-eightCorrodes thin and snaps, often with no cracking, so failure can go unnoticed
Double triangleThicker wire formed into two trianglesThins and snaps like a butterfly tie, rather than swelling

Strip ties are the ones that crack walls, because rust takes up at least twice the volume of the steel it replaces. Wire ties are the ones that fail quietly. Both are explained on the wall tie failure page.

Modern stainless ties

New walls use austenitic stainless steel ties made to BS EN 845-1. In the UK, PD 6697 sorts them by duty, from Type 1 (heavy duty) to Type 4 (light duty, for houses up to 10m high). Houses usually take Type 2 (general purpose) or Type 4 ties. Merchants sell them by this type number and by length.

Many modern ties also have a clip to hold partial-fill cavity insulation boards against the inner leaf.

Remedial wall ties

When original ties fail, new ones are fitted from outside without taking the wall down. There are three main kinds, all stainless steel:

Lightweight aerated concrete block in the inner leaf is soft, so it often needs a resin-bonded tie or one designed for that block to get a secure fixing. The right choice depends on what both leaves are built from, which is something a wall tie survey establishes. See how failed ties are replaced for the full process.

Timber frame walls

Not every house with a brick outside has two masonry leaves. In a timber frame house the brick outer leaf is tied back to the timber frame, not to block or brick. These walls use timber frame wall ties: stainless steel ties fixed to the studs and bedded in the brick joints, flexible enough to allow for the timber shrinking while the brickwork does not. Remedial ties for masonry are not a straight swap here, so tell any installer if your house is timber framed.

Wall tie spacing

Approved Document A sets the usual spacing for new masonry walls in England: ties at 900mm horizontal centres and 450mm vertical centres. Remedial ties are normally fitted to a similar density.

WhereHorizontal centresVertical centres
General wall, any cavity of 50mm or more900mm450mm
Within 225mm of openings, movement joints and roof vergesn/a300mm maximum

Ties in neighbouring rows are staggered, so the pattern works out at about two and a half ties per square metre. A wider cavity does not change the spacing, but it needs a longer tie. Six courses (rows) of standard brick come to about 450mm, which is why the cracks from failed strip ties often repeat every sixth course.

Choosing ties for new work

If you are building a new cavity wall or an extension, rather than repairing an old one:

We do not sell ties. Your building control officer or the tie manufacturer can confirm the right tie for your wall.

Working out what you have

A metal wall tie bridging a cavity wall, seen through a borescope, with mortar droppings caught on it.
A wall tie inside a cavity, seen through a borescope. This is how a survey shows which ties a wall has and what state they are in. Photo: Insul8.

Questions people ask

What is the standard wall tie spacing?

One tie every 900mm horizontally and every 450mm vertically, staggered, with extra ties within 225mm of the edges of openings, movement joints and roof verges at no more than 300mm vertical spacing. Wider cavities need longer ties rather than closer spacing.

What type of wall tie is used today?

Austenitic stainless steel ties made to BS EN 845-1. For housing, these are usually classed by duty, from heavy to light, under PD 6697.

What are helical wall ties?

Spiral stainless steel ties used for remedial work. They are fixed from outside through a small pilot hole and grip both leaves along their length, so no resin or expansion sleeve is needed.

Can I tell what wall ties I have without opening the wall?

Not for certain. A metal detector shows where the ties are, but seeing what type they are and their condition needs a borescope through a small drilled hole, or a brick taken out.